--  Module  : SPECTRACOM-VERSASYNC-REG.mib
--  Date    : 26 April 2015
--  Authors : Herve Echelard, Mark Goodlein
--  Purpose : This MIB defines the xSync product module for the private
--            Spectracom MIB.
--
--  Copyright(C) 2010-2016 Spectracom Corporation.
--  All Rights Reserved.
--..............................................................................

SPECTRACOM-XSYNC-MIB DEFINITIONS ::= BEGIN

IMPORTS
    MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE, Integer32, Unsigned32
        FROM SNMPv2-SMI
    MODULE-COMPLIANCE, OBJECT-GROUP, NOTIFICATION-GROUP
        FROM SNMPv2-CONF
    DisplayString
        FROM SNMPv2-TC
    specModules, specProducts
        FROM SPECTRACOM-GLOBAL-REG-MIB;

spectracomxSyncMibModule MODULE-IDENTITY
--               "YYYYMMDDHHMMZ"
    LAST-UPDATED "202212091030Z"
    ORGANIZATION "Spectracom"
    CONTACT-INFO
        "Postal: Orolia USA, Inc. dba Spectracom
                 45 Becker Road, Suite A
                 West Henrietta, NY 14586 USA
         Tel:    +1 (585) 321-5800
         Fax:    +1 (585) 321-5218
         Email:  timingsupport@orolia.com"
    DESCRIPTION
        "Spectracom Corporation's xSync MIB."

    REVISION    "202212091030Z"
    DESCRIPTION
        "Rev 1.13 - Added the ssSysSetManualTime and ssSysStaDisciplining objects."
    REVISION    "202206200931Z"
    DESCRIPTION
        "Rev 1.12 - Added Hot Swap related objects and traps."
    REVISION    "202201101601Z"
    DESCRIPTION
        "Rev 1.11 - Added Broadshield related objects and traps."
    REVISION    "202201070000Z"
    DESCRIPTION
        "Rev 1.10 - Updated address and email."
    REVISION    "201710041151Z"
    DESCRIPTION
        "Rev 1.9 - Change VersaSync prefix to xSync for MIB and OIDs."
    REVISION    "201511101300Z"
    DESCRIPTION
        "Rev 1.8 - Added Temperature related objects and traps."
    REVISION    "201502201924Z"
    DESCRIPTION
        "Rev 1.7 - Added ssSysStaSerial object."
    REVISION    "201410081453Z"
    DESCRIPTION
        "Rev 1.6 - Added ssRefMgmtTimeValid and ssRefMgmt1PPSValid."
    REVISION    "201306171453Z"
    DESCRIPTION
        "Rev 1.5 - Updated address."
    REVISION     "201202020000Z"
    DESCRIPTION
        "Rev 1.4 - Added the ssSysStaDateTime object."

    REVISION     "201110310000Z"
    DESCRIPTION
        "Rev 1.3 - Added the Reboot event."

    REVISION     "201103280000Z"
    DESCRIPTION
        "Rev 1.2 - Added new column as index for GPS table.
                 - Changed enumerations to remove (0) values.
                 - Changed size of reference identifier strings from 20 to 5.
                 - Added Reference Managemant objects.
                 - Added System Control objects.
                 - Replaced misspelled Freqency with Frequency.
                 - Fixed the varbind included with the ssEvtV2MajorAlarm event."

    REVISION     "201007260000Z"
    DESCRIPTION
        "Rev 1.1 - Updates to variable descriptions."

    REVISION     "201004170000Z"
    DESCRIPTION
        "Rev 1.0 - Initial version of Spectracom's VersaSync MIB module
                   SPECTRACOM-VERSASYNC-MIB."

    ::= { specModules 4 }

--******************************************************************************
-- Tree definition
--..............................................................................

specxSyncMIB       OBJECT IDENTIFIER ::= { specProducts 2 }

-- specxSyncMIB subtree
specxSyncConfs      OBJECT IDENTIFIER ::= { specxSyncMIB 1 }
specxSyncObjs       OBJECT IDENTIFIER ::= { specxSyncMIB 2 }
specxSyncEvents     OBJECT IDENTIFIER ::= { specxSyncMIB 3 }

--specxSyncConfs subtree
specxSyncGroups     OBJECT IDENTIFIER ::= { specxSyncConfs 1 }
specxSyncCompl      OBJECT IDENTIFIER ::= { specxSyncConfs 2 }

--specxSyncObjs subtree
ssSystemStatusObjs      OBJECT IDENTIFIER ::= { specxSyncObjs 1 }
ssGpsRefStatusObjs      OBJECT IDENTIFIER ::= { specxSyncObjs 2 }
ssOptionCardObjs        OBJECT IDENTIFIER ::= { specxSyncObjs 3 }
ssReferenceMgmtObjs     OBJECT IDENTIFIER ::= { specxSyncObjs 4 }
ssSystemControlObjs     OBJECT IDENTIFIER ::= { specxSyncObjs 5 }
ssHotSwapObjs           OBJECT IDENTIFIER ::= { specxSyncObjs 6 }

--specxSyncEvents subtree
ssEventsV2              OBJECT IDENTIFIER ::= { specxSyncEvents 0 }

--ssHotSwapObjs subtree
ssHotSwapBay1     OBJECT IDENTIFIER ::= { ssHotSwapObjs 1 }
ssHotSwapBay2     OBJECT IDENTIFIER ::= { ssHotSwapObjs 2 }


--******************************************************************************
-- ssSystemStatusObjs Objects [enterprises.18837.3.2.2.1.x]
--..............................................................................

ssSysStaPowerDC         OBJECT-TYPE
    SYNTAX              INTEGER { ok(1),
                                  alarm(2),
                                  none(3) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "General status of the DC power input."
    ::= { ssSystemStatusObjs 2 }

ssSysStaTimeReference   OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(5))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "The chosen reference source and instance for time of day information.
         This identifier typically consists of a 3-character reference string
         followed by a single-digit instance number.  It indicates which
         reference is currently being used by the system for time of day.
         The following is a list of common reference identifiers/instances:
             gps    GPS reference             (i.e. gps0, gps1, etc.)
             ira    IRIG AM reference         (i.e. ira0, ira1, etc.)
             ird    IRIG DCLS reference       (i.e. ird0, ird1, etc.)
             irg    IRIG AM/DCLS reference    (i.e. irg0, irg1, etc.)
             asc    ASCII time code reference (i.e. asc0, asc1, etc.)
             epp    [External] 1PPS reference (i.e. epp0, epp1, etc.)
             frq    Frequency reference       (i.e. frq0, frq1, etc.)
             hst    Host system reference     (i.e. hst0, hst1, etc.)
             self   Internal reference"
    ::= { ssSystemStatusObjs 3 }

ssSysSta1PPSReference   OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(5))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "The chosen reference source and instance of 1 pulse-per-second
         signal.  This identifier typically consists of a 3-character reference
         string followed by a single-digit instance number.  It indicates which
         reference is currently being used by the system for 1PPS.
         The following is a list of common reference identifiers/instances:
             gps    GPS reference             (i.e. gps0, gps1, etc.)
             ira    IRIG AM reference         (i.e. ira0, ira1, etc.)
             ird    IRIG DCLS reference       (i.e. ird0, ird1, etc.)
             irg    IRIG AM/DCLS reference    (i.e. irg0, irg1, etc.)
             asc    ASCII time code reference (i.e. asc0, asc1, etc.)
             epp    [External] 1PPS reference (i.e. epp0, epp1, etc.)
             frq    Frequency reference       (i.e. frq0, frq1, etc.)
             hst    Host system reference     (i.e. hst0, hst1, etc.)
             self   Internal reference"
    ::= { ssSystemStatusObjs 4 }

ssSysStaSyncState       OBJECT-TYPE
    SYNTAX              INTEGER { sync(1),
                                  nosync(2) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Status of the unit's synchronization with its time/1pps references."
    ::= { ssSystemStatusObjs 5 }

ssSysStaHoldoverState   OBJECT-TYPE
    SYNTAX              INTEGER { inHoldover(1),
                                  notInHoldover(2) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "When in holdover, the unit has lost its references, is fly-wheeling
         using the oscillator, and the time and frequency outputs are still
         within specifications."
    ::= { ssSystemStatusObjs 6 }

ssSysStaTfom            OBJECT-TYPE
    SYNTAX              Unsigned32(0..15)
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This indicates the estimated time error of the unit's internal time
         with respect to the selected time/1pps references.  The following
         table identifies the ranges per TFOM value:
             0:  TFOM is not defined, ETE is unknown
             1:              ETE <=   1 nsec
             2:     1 nsec < ETE <=  10 nsec
             3:    10 nsec < ETE <= 100 nsec
             4:   100 nsec < ETE <=   1 usec
             5:     1 usec < ETE <=  10 usec
             6:    10 usec < ETE <= 100 usec
             7:   100 usec < ETE <=   1 msec
             8:     1 msec < ETE <=  10 msec
             9:    10 msec < ETE <= 100 msec
             10:  100 msec < ETE <=   1 sec
             11:    1 sec  < ETE <=  10 sec
             12:   10 sec  < ETE <=  100 sec
             13:  100 sec  < ETE <= 1000 sec
             14: 1000 sec  < ETE <= 10000 sec
             15:             ETE >  10000 sec"
    ::= { ssSystemStatusObjs 7 }

ssSysStaEstPhaseError   OBJECT-TYPE
    SYNTAX              Integer32
    UNITS               "nanoseconds"
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This indicates the estimated phase error (magnitude) of the unit's
         internal 1PPS with respect to the selected 1pps reference."
    ::= { ssSystemStatusObjs 8 }

ssSysStaEstFreqError    OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(20))
    UNITS               "hertz"
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This indicates the estimated frequency error (magnitude) of the unit's
         internal 10 MHz oscillator with respect to the selected 1pps
         reference."
    ::= { ssSystemStatusObjs 9 }

ssSysStaTimeScale       OBJECT-TYPE
    SYNTAX              INTEGER { utc(1),
                                  tai(2),
                                  gps(3) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Time scale of the unit's timing system."
    ::= { ssSystemStatusObjs 10 }

ssSysStaVersion         OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(20))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This indicates the current overall system software version."
    ::= { ssSystemStatusObjs 11 }

ssSysStaTimingVersion   OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(20))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This indicates the current timing system software version."
    ::= { ssSystemStatusObjs 12 }

ssSysStaMinorAlarm      OBJECT-TYPE
    SYNTAX              INTEGER { pending(1),
                                  clear(2) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This indicates whether or not a minor alarm is currently active.
         The value of pending indicates that the alarm condition is active and
         is pending resolution."
    ::= { ssSystemStatusObjs 13 }

ssSysStaMajorAlarm      OBJECT-TYPE
    SYNTAX              INTEGER { pending(1),
                                  clear(2) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This indicates whether or not a major alarm is currently pending.
         The value of pending indicates that the alarm condition is active and
         is pending resolution."
    ::= { ssSystemStatusObjs 14 }

ssSysStaDateTime        OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(30))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This indicates the current system date and time in the following
         format:
                 YYYY DDD HH:MM:SS.NNNNNNNNN
         where:
                 YYYY      = Year
                 DDD       = Day of Year
                 HH        = Hour
                 MM        = Minute
                 SS        = Second
                 NNNNNNNNN = Subseconds"
    ::= { ssSystemStatusObjs 15 }

ssSysStaSerial          OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(20))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This indicates the system serial number."
    ::= { ssSystemStatusObjs 16 }

ssSysStaOscTemp         OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(20))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This unit's Oscillator Temperature in degrees Celsius."
    ::= { ssSystemStatusObjs 17 }

ssSysStaBrdTemp         OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(20))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This unit's Board Temperature in degrees Celsius."
    ::= { ssSystemStatusObjs 18 }

ssSysStaCpuTemp         OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(20))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This unit's CPU Temperature in degrees Celsius."
    ::= { ssSystemStatusObjs 19 }

ssSysStaMinorAlarmCauses    OBJECT-TYPE
    SYNTAX                  DisplayString(SIZE(128))
    MAX-ACCESS              read-only
    STATUS                  current
    DESCRIPTION
        "This units Minor alarm causes causes as a list separated with a | sign
         Example : MAX_TEMP_MINOR|ENTER_HOLDOVER|MIN_SAT_MINOR"
    ::= { ssSystemStatusObjs 20 }

ssSysStaMajorAlarmCauses    OBJECT-TYPE
    SYNTAX                  DisplayString(SIZE(128))
    MAX-ACCESS              read-only
    STATUS                  current
    DESCRIPTION
        "This units Major alarm causes as a list separated with a | sign
         Example : MAX_TEMP_MAJOR|MIN_SAT_MAJOR|TIMING_HW_ERR"
    ::= { ssSystemStatusObjs 21 }

ssSysStaBshJammingState OBJECT-TYPE
    SYNTAX              INTEGER { active(1),
                                  noactive(2) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This indicates the state of jamming"
    ::= { ssSystemStatusObjs 22 }

ssSysStaBshSpoofingState OBJECT-TYPE
    SYNTAX              INTEGER { active(1),
                                  noactive(2) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This indicates the state of spoofing"
    ::= { ssSystemStatusObjs 23 }

ssSysStaDisciplining    OBJECT-TYPE
    SYNTAX              INTEGER { none(0),
                                  warmup(1),
                                  calibration(2),
                                  trackSetup(3),
                                  trackLock(4),
                                  freerun(5),
                                  fault(6)}
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This indicates whether or not the internal oscillateur is currently being disciplined."
    ::= { ssSystemStatusObjs 24 }

--******************************************************************************
-- ssGpsRefStatusObjs Objects [enterprises.18837.3.2.2.2.x]
--..............................................................................

ssGpsRefTable           OBJECT-TYPE
    SYNTAX              SEQUENCE OF SsGpsRefTableEntry
    MAX-ACCESS          not-accessible
    STATUS              current
    DESCRIPTION
        "This table contains status for all GPS references that are present in
         in system."
    ::= { ssGpsRefStatusObjs 1 }

ssGpsRefTableEntry      OBJECT-TYPE
    SYNTAX              SsGpsRefTableEntry
    MAX-ACCESS          not-accessible
    STATUS              current
    DESCRIPTION
        "A table entry (row) in the GPS reference table."
    INDEX               { ssGpsRefRow }
    ::= { ssGpsRefTable 1 }

SsGpsRefTableEntry ::= SEQUENCE {
        ssGpsRefRow           Unsigned32,
        ssGpsRefInstance      Unsigned32,
        ssGpsReference        DisplayString,
        ssGpsRefTimeValid     INTEGER,
        ssGpsRef1ppsValid     INTEGER,
        ssGpsRefRcvMode       INTEGER,
        ssGpsRefDynMode       INTEGER,
        ssGpsRefNumSats       Unsigned32,
        ssGpsRefPdop          DisplayString,
        ssGpsRefHdop          DisplayString,
        ssGpsRefVdop          DisplayString,
        ssGpsRefTdop          DisplayString,
        ssGpsRefLatitude      DisplayString,
        ssGpsRefLongitude     DisplayString,
        ssGpsRefAltitude      DisplayString,
        ssGpsRefOffset        Integer32,
        ssGpsRefAntennaState  INTEGER }

ssGpsRefRow             OBJECT-TYPE
    SYNTAX              Unsigned32(1..8)
    MAX-ACCESS          not-accessible
    STATUS              current
    DESCRIPTION
        "This is the index value for each table row."
    ::= { ssGpsRefTableEntry 1 }

ssGpsRefInstance        OBJECT-TYPE
    SYNTAX              Unsigned32(0..7)
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This is the unique instance for each GPS reference."
    ::= { ssGpsRefTableEntry 2 }

ssGpsReference          OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(5))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "The GPS reference identifier."
    ::= { ssGpsRefTableEntry 3 }

ssGpsRefTimeValid       OBJECT-TYPE
    SYNTAX              INTEGER { valid(1),
                                  invalid(2) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This indicates whether this GPS reference has can provide valid time."
    ::= { ssGpsRefTableEntry 4 }

ssGpsRef1ppsValid       OBJECT-TYPE
    SYNTAX              INTEGER { valid(1),
                                  invalid(2) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This indicates whether this GPS reference has can provide valid 1PPS."
    ::= { ssGpsRefTableEntry 5 }

ssGpsRefRcvMode         OBJECT-TYPE
    SYNTAX              INTEGER { singleSat(1),
                                  standard(2),
                                  continuous(3),
                                  averaging(4),
                                  timeOnly(5),
                                  standby(6),
                                  selfTest(7) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This indicates the current GPS reference operating mode."
    ::= { ssGpsRefTableEntry 6 }

ssGpsRefDynMode         OBJECT-TYPE
    SYNTAX              INTEGER { land(1),
                                  sea(2),
                                  air(3),
                                  stationary(4) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This indicates the current GPS reference dynamics mode.  Note that the
         land, sea, and air modes are for mobile operation."
    ::= { ssGpsRefTableEntry 7 }

ssGpsRefNumSats         OBJECT-TYPE
    SYNTAX              Unsigned32
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This is the number of satellites currently used in position and time
         fix calculations."
    ::= { ssGpsRefTableEntry 8 }

ssGpsRefPdop            OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(20))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Positional dilution of precision."
    ::= { ssGpsRefTableEntry 9 }

ssGpsRefHdop            OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(20))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Horizontal dilution of precision."
    ::= { ssGpsRefTableEntry 10 }

ssGpsRefVdop            OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(20))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Vertical dilution of precision."
    ::= { ssGpsRefTableEntry 11 }

ssGpsRefTdop            OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(20))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Temporal dilution of precision."
    ::= { ssGpsRefTableEntry 12 }

ssGpsRefLatitude        OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(20))
    UNITS               "degrees"
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This is the latitude location of the GPS antenna in radians."
    ::= { ssGpsRefTableEntry 13 }

ssGpsRefLongitude       OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(20))
    UNITS               "degrees"
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This is the longitude location of the GPS antenna in radians."
    ::= { ssGpsRefTableEntry 14 }

ssGpsRefAltitude       OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(20))
    UNITS               "meters"
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This is the altitude of the GPS antenna in meters above mean sea
         level."
    ::= { ssGpsRefTableEntry 15 }

ssGpsRefOffset          OBJECT-TYPE
    SYNTAX              Integer32
    UNITS               "nanoseconds"
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This is the offset applied to the GPS reference 1PPS in nanoseconds."
    ::= { ssGpsRefTableEntry 16 }

ssGpsRefAntennaState    OBJECT-TYPE
    SYNTAX              INTEGER { ok(1),
                                  short(2),
                                  open(3),
                                  unknown(4) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This indicates the current GPS reference antenna state."
    ::= { ssGpsRefTableEntry 17 }

--******************************************************************************
-- ssOptionCardObjs Objects [enterprises.18837.3.2.2.3.x]
--..............................................................................

--******************************************************************************
-- ssReferenceMgmtObjs Objects [enterprises.18837.3.2.2.4.x]
--..............................................................................

ssRefMgmtTable          OBJECT-TYPE
    SYNTAX              SEQUENCE OF SsRefMgmtTableEntry
    MAX-ACCESS          not-accessible
    STATUS              current
    DESCRIPTION
        "This table contains time and 1PPS reference pairs and the priority of
         those pairs withing the timing system.  Priority value 1 is highest."
    ::= { ssReferenceMgmtObjs 1 }

ssRefMgmtTableEntry     OBJECT-TYPE
    SYNTAX              SsRefMgmtTableEntry
    MAX-ACCESS          not-accessible
    STATUS              current
    DESCRIPTION
        "A table entry (row) in the GPS reference table."
    INDEX               { ssRefMgmtRow }
    ::= { ssRefMgmtTable 1 }

SsRefMgmtTableEntry ::= SEQUENCE {
        ssRefMgmtRow       Unsigned32,
        ssRefMgmtIndex     Unsigned32,
        ssRefMgmtState     INTEGER,
        ssRefMgmtPriority  Unsigned32,
        ssRefMgmtTime      DisplayString,
        ssRefMgmt1PPS      DisplayString,
        ssRefMgmtTimeValid INTEGER,
        ssRefMgmt1PPSValid INTEGER}

ssRefMgmtRow            OBJECT-TYPE
    SYNTAX              Unsigned32(1..15)
    MAX-ACCESS          not-accessible
    STATUS              current
    DESCRIPTION
        "This is the index value for each table row."
    ::= { ssRefMgmtTableEntry 1 }

ssRefMgmtIndex          OBJECT-TYPE
    SYNTAX              Unsigned32(0..14)
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This is the system index for each table entry.  This is the index
         value used internally by the timing system to address each row of the
         table."
    ::= { ssRefMgmtTableEntry 2 }

ssRefMgmtState          OBJECT-TYPE
    SYNTAX              INTEGER { enabled(1),
                                  disabled(2) }
    MAX-ACCESS          read-write
    STATUS              current
    DESCRIPTION
        "This is the enable/disable state for each row."
    ::= { ssRefMgmtTableEntry 3 }

ssRefMgmtPriority       OBJECT-TYPE
    SYNTAX              Unsigned32(1..15)
    MAX-ACCESS          read-write
    STATUS              current
    DESCRIPTION
        "This is the priority indicator for each reference pair.  Priority
         value 1 is highest."
    ::= { ssRefMgmtTableEntry 4 }

ssRefMgmtTime           OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(5))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This is the time reference identifier.    This identifier typically
         consists of a 3-character reference string followed by a single-digit
         instance number.  It indicates a reference to be used by the system
         for time.  The following is a list of common reference
         identifiers/instances:
             gps    GPS reference             (i.e. gps0, gps1, etc.)
             ira    IRIG AM reference         (i.e. ira0, ira1, etc.)
             ird    IRIG DCLS reference       (i.e. ird0, ird1, etc.)
             irg    IRIG AM/DCLS reference    (i.e. irg0, irg1, etc.)
             asc    ASCII time code reference (i.e. asc0, asc1, etc.)
             epp    [External] 1PPS reference (i.e. epp0, epp1, etc.)
             frq    Frequency reference       (i.e. frq0, frq1, etc.)
             hst    Host system reference     (i.e. hst0, hst1, etc.)
             self   Internal reference"
    ::= { ssRefMgmtTableEntry 5 }

ssRefMgmt1PPS           OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(5))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This is the 1PPS reference identifier.    This identifier typically
         consists of a 3-character reference string followed by a single-digit
         instance number.  It indicates a reference to be used by the system
         for 1PPS.  The following is a list of common reference
         identifiers/instances:
             gps    GPS reference             (i.e. gps0, gps1, etc.)
             ira    IRIG AM reference         (i.e. ira0, ira1, etc.)
             ird    IRIG DCLS reference       (i.e. ird0, ird1, etc.)
             irg    IRIG AM/DCLS reference    (i.e. irg0, irg1, etc.)
             asc    ASCII time code reference (i.e. asc0, asc1, etc.)
             epp    [External] 1PPS reference (i.e. epp0, epp1, etc.)
             frq    Frequency reference       (i.e. frq0, frq1, etc.)
             hst    Host system reference     (i.e. hst0, hst1, etc.)
             self   Internal reference"
    ::= { ssRefMgmtTableEntry 6 }

ssRefMgmtTimeValid       OBJECT-TYPE
    SYNTAX              INTEGER { valid(1),
                                  invalid(2) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This indicates whether the input reference has can provide valid time for each row."
    ::= { ssRefMgmtTableEntry 7 }

ssRefMgmt1PPSValid       OBJECT-TYPE
    SYNTAX              INTEGER { valid(1),
                                  invalid(2) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This indicates whether the input reference has can provide valid 1PPS for each row."
    ::= { ssRefMgmtTableEntry 8 }

--******************************************************************************
-- ssSystemControlObjs Objects [enterprises.18837.3.2.2.5.x]
--..............................................................................

ssSysCtrlCommand        OBJECT-TYPE
    SYNTAX              INTEGER { idle(1),
                                  update(2),
                                  forceupdate(3),
                                  reboot(4) }
    MAX-ACCESS          read-write
    STATUS              current
    DESCRIPTION
        "This allows simple control commands to be applied to the system.
         Commands (other than idle) issued via this object will take effect 60
         seconds after the command is written.  The command descriptions are as
         follows:
             idle:        Cancel a pending update, forceupdate, or reboot
                            command.
             update:      Update the system software/firmware using the update
                            file specified by the ssSysUpdateFile object.  Any
                            subsystem that matches or exceeds the version in
                            the update file will not be updated.
             forceupdate: Update the system software/firmware using the update
                            file specified by the ssSysUpdateFile object.  All
                            subsystems contained within the update file will be
                            updated regardless of their current version.
             reboot:      Shutdown and reboot the system."
    ::= { ssSystemControlObjs 1 }

ssSysUpdateFile         OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(80))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "This indicates the last (alphabetical) file name of update bundles
         residing in the administrator (spadmin) home directory.  This file
         will be used to update the system if an update or forceupdate command
         is set via the ssSysCtrlCommand object."
    ::= { ssSystemControlObjs 2 }

ssSysSetManualTime      OBJECT-TYPE
    SYNTAX              OCTET STRING (SIZE(0..64))
    MAX-ACCESS          write-only
    STATUS              current
    DESCRIPTION
        "Set the system time with a user time.
         The format is : <year> <doy> <hour> <minute> <second>.
         Will always return an empty string when read."
    ::= { ssSystemControlObjs 3 }

--******************************************************************************
-- ssHotSwapObjs Object [enterprises.18837.3.2.2.6.x]
--..............................................................................

ssHotSwapOverallHealth OBJECT-TYPE
    SYNTAX              INTEGER { ok(0),
                                  noMonitoring(1),
                                  warning(2),
                                  fault(3) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap general status."
    ::= { ssHotSwapObjs 0 }

ssHotSwapBay1Health OBJECT-TYPE
    SYNTAX              INTEGER { ok(0),
                                  noMonitoring(1),
                                  warning(2),
                                  fault(3) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 1's Status."
    ::= { ssHotSwapBay1 0 }

ssHotSwapBay1Type OBJECT-TYPE
    SYNTAX              INTEGER { ac(0),
                                  dc12(1),
                                  dc24(2),
                                  none(3) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 1's power input type."
    ::= { ssHotSwapBay1 1 }

ssHotSwapBay1Presence OBJECT-TYPE
    SYNTAX              INTEGER { notInstalled(0),
                                  installed(1) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 1's presence."
    ::= { ssHotSwapBay1 2 }

ssHotSwapBay1Voltage OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(20))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 1's voltage (V)."
    ::= { ssHotSwapBay1 3 }

ssHotSwapBay1Current OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(20))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 1's current (A)."
    ::= { ssHotSwapBay1 4 }

ssHotSwapBay1FanEnabled OBJECT-TYPE
    SYNTAX              INTEGER { disabled(0),
                                   enabled(1) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 1's fan status."
    ::= { ssHotSwapBay1 5 }

ssHotSwapBay1FanSpeed OBJECT-TYPE
    SYNTAX              INTEGER
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 1's fan speed (RPM)."
    ::= { ssHotSwapBay1 6 }

ssHotSwapBay1Temp OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(20))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 1's temperature (°C)."
    ::= { ssHotSwapBay1 7 }

ssHotSwapBay1VoltageInRange OBJECT-TYPE
    SYNTAX              INTEGER { outOfRange(0),
                                  inRange(1) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 1's voltage In range indicator."
    ::= { ssHotSwapBay1 8 }

ssHotSwapBay1CurrentInRange OBJECT-TYPE
    SYNTAX              INTEGER { outOfRange(0),
                                  inRange(1) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 1's current In range indicator."
    ::= { ssHotSwapBay1 9 }

ssHotSwapBay1FanSpeedInRange OBJECT-TYPE
    SYNTAX              INTEGER { outOfRange(0),
                                  inRange(1) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 1's fan speed In range indicator."
    ::= { ssHotSwapBay1 10 }

ssHotSwapBay1TempInRange OBJECT-TYPE
    SYNTAX              INTEGER { outOfRange(0),
                                  inRange(1) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 1's temperature In range indicator."
    ::= { ssHotSwapBay1 11 }

ssHotSwapBay2Health OBJECT-TYPE
    SYNTAX              INTEGER { ok(0),
                                  noMonitoring(1),
                                  warning(2),
                                  fault(3) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 2's Status."
    ::= { ssHotSwapBay2 0 }

ssHotSwapBay2Type OBJECT-TYPE
    SYNTAX              INTEGER { ac(0),
                                  dc12(1),
                                  dc24(2),
                                  none(3) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 2's power input type."
    ::= { ssHotSwapBay2 1 }

ssHotSwapBay2Presence OBJECT-TYPE
    SYNTAX              INTEGER { notInstalled(0),
                                  installed(1) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 2's presence."
    ::= { ssHotSwapBay2 2 }

ssHotSwapBay2Voltage OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(20))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 2's voltage (V)."
    ::= { ssHotSwapBay2 3 }

ssHotSwapBay2Current OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(20))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 2's current (A)."
    ::= { ssHotSwapBay2 4 }

ssHotSwapBay2FanEnabled OBJECT-TYPE
    SYNTAX              INTEGER { disabled(0),
                                   enabled(1) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 2's fan status."
    ::= { ssHotSwapBay2 5 }

ssHotSwapBay2FanSpeed OBJECT-TYPE
    SYNTAX              INTEGER
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 2's fan speed (RPM)."
    ::= { ssHotSwapBay2 6 }

ssHotSwapBay2Temp OBJECT-TYPE
    SYNTAX              DisplayString(SIZE(20))
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 2's temperature (°C)."
    ::= { ssHotSwapBay2 7 }

ssHotSwapBay2VoltageInRange OBJECT-TYPE
    SYNTAX              INTEGER { outOfRange(0),
                                  inRange(1) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 2's voltage In range indicator."
    ::= { ssHotSwapBay2 8 }

ssHotSwapBay2CurrentInRange OBJECT-TYPE
    SYNTAX              INTEGER { outOfRange(0),
                                  inRange(1) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 2's current In range indicator."
    ::= { ssHotSwapBay2 9 }

ssHotSwapBay2FanSpeedInRange OBJECT-TYPE
    SYNTAX              INTEGER { outOfRange(0),
                                  inRange(1) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 2's fan speed In range indicator."
    ::= { ssHotSwapBay2 10 }

ssHotSwapBay2TempInRange OBJECT-TYPE
    SYNTAX              INTEGER { outOfRange(0),
                                  inRange(1) }
    MAX-ACCESS          read-only
    STATUS              current
    DESCRIPTION
        "Hot Swap Bay 2's temperature In range indicator."
    ::= { ssHotSwapBay2 11 }

--******************************************************************************
-- ssEventsV2 [enterprises.18837.3.2.3.x]
--..............................................................................

ssEvtV2TimeSync         NOTIFICATION-TYPE
    OBJECTS             { ssSysStaSyncState }
    STATUS              current
    DESCRIPTION
        "The unit has either entered or left the synchronized state."
    ::= { ssEventsV2 1 }

ssEvtV2Holdover         NOTIFICATION-TYPE
    OBJECTS             { ssSysStaHoldoverState }
    STATUS              current
    DESCRIPTION
        "The unit has either entered or left the holdover state."
    ::= { ssEventsV2 2 }

ssEvtV2FrequencyError   NOTIFICATION-TYPE
    OBJECTS             { ssSysStaEstFreqError }
    STATUS              current
    DESCRIPTION
        "The frequency output error exceeds specifications."
    ::= { ssEventsV2 3 }

ssEvtV2FrequencyOK      NOTIFICATION-TYPE
    OBJECTS             { ssSysStaEstFreqError }
    STATUS              current
    DESCRIPTION
        "The frequency output error meets specifications."
    ::= { ssEventsV2 4 }

ssEvtV2UserMinorAlarm   NOTIFICATION-TYPE
    OBJECTS             { ssGpsRefNumSats }
    STATUS              current
    DESCRIPTION
        "The user-programmable minor alarm timeout has been asserted."
    ::= { ssEventsV2 5 }

ssEvtV2UserMinorClear   NOTIFICATION-TYPE
    OBJECTS             { ssGpsRefNumSats }
    STATUS              current
    DESCRIPTION
        "The user-programmable minor alarm timeout has been reset."
    ::= { ssEventsV2 6 }

ssEvtV2UserMajorAlarm   NOTIFICATION-TYPE
    OBJECTS             { ssGpsRefNumSats }
    STATUS              current
    DESCRIPTION
        "The user-programmable major alarm timeout has been asserted."
    ::= { ssEventsV2 7 }

ssEvtV2UserMajorClear   NOTIFICATION-TYPE
    OBJECTS             { ssGpsRefNumSats }
    STATUS              current
    DESCRIPTION
        "The user-programmable major alarm timeout has been reset."
    ::= { ssEventsV2 8 }

ssEvtV2GpsAntenna       NOTIFICATION-TYPE
    OBJECTS             { ssGpsRefAntennaState }
    STATUS              current
    DESCRIPTION
        "The GPS antenna state has changed."
    ::= { ssEventsV2 9 }

ssEvtV2MinorAlarm       NOTIFICATION-TYPE
    OBJECTS             { ssSysStaMinorAlarm }
    STATUS              current
    DESCRIPTION
        "The system minor alarm has changed state."
    ::= { ssEventsV2 10 }

ssEvtV2MajorAlarm       NOTIFICATION-TYPE
    OBJECTS             { ssSysStaMajorAlarm }
    STATUS              current
    DESCRIPTION
        "The system major alarm has changed state."
    ::= { ssEventsV2 11 }

ssEvtV2RefChange        NOTIFICATION-TYPE
    OBJECTS             { ssSysStaTimeReference, ssSysSta1PPSReference }
    STATUS              current
    DESCRIPTION
        "The selected time reference has changed."
    ::= { ssEventsV2 12 }

ssEvtV21ppsError        NOTIFICATION-TYPE
    OBJECTS             { ssSysStaTimeReference, ssSysSta1PPSReference }
    STATUS              current
    DESCRIPTION
        "The 1PPS output error exceeds specifications."
    ::= { ssEventsV2 13 }

ssEvtV21ppsOK           NOTIFICATION-TYPE
    OBJECTS             { ssSysStaTimeReference, ssSysSta1PPSReference }
    STATUS              current
    DESCRIPTION
        "The 1PPS output error meets specifications."
    ::= { ssEventsV2 14 }

ssEvtV2HwError          NOTIFICATION-TYPE
    OBJECTS             { ssSysStaTimeReference, ssSysSta1PPSReference }
    STATUS              current
    DESCRIPTION
        "The timing system hardware is impaired."
    ::= { ssEventsV2 15 }

ssEvtV2OscillatorAlarm  NOTIFICATION-TYPE
    OBJECTS             { ssSysStaEstFreqError }
    STATUS              current
    DESCRIPTION
        "The oscillator is requires maintenance.  This typically indicates that
         the oscillator is within 10% of the edge its adjustable range (TCXO
         and OCXO) or the oscillator module lamp needs service (Rubidium)."
    ::= { ssEventsV2 16 }

ssEvtV2OscillatorOK     NOTIFICATION-TYPE
    OBJECTS             { ssSysStaEstFreqError }
    STATUS              current
    DESCRIPTION
        "The oscillator no longer requires maintenance.  This typically
         indicates that the oscillator adjustment value has changed and is now
         greater than 10% from the edge of its adjustable range."
    ::= { ssEventsV2 17 }

ssEvtV2Reboot           NOTIFICATION-TYPE
    STATUS              current
    DESCRIPTION
        "The system has rebooted."
    ::= { ssEventsV2 18 }

ssEvtV2MaxTempMinorAlarm NOTIFICATION-TYPE
    OBJECTS             { ssSysStaCpuTemp }
    STATUS              current
    DESCRIPTION
        "The maximum temperature minor alarm has been asserted."
    ::= { ssEventsV2 19 }

ssEvtV2MaxTempMinorClear NOTIFICATION-TYPE
    OBJECTS             { ssSysStaCpuTemp }
    STATUS              current
    DESCRIPTION
        "The maximum temperature minor alarm has been reset."
    ::= { ssEventsV2 20 }

ssEvtV2MaxTempMajorAlarm NOTIFICATION-TYPE
    OBJECTS             { ssSysStaCpuTemp }
    STATUS              current
    DESCRIPTION
        "The maximum temperature major alarm has been asserted."
    ::= { ssEventsV2 21 }

ssEvtV2MaxTempMajorClear NOTIFICATION-TYPE
    OBJECTS             { ssSysStaCpuTemp }
    STATUS              current
    DESCRIPTION
        "The maximum temperature major alarm has been reset."
    ::= { ssEventsV2 22 }

ssEvtV2BshMajorAlarm NOTIFICATION-TYPE
    OBJECTS             { ssSysStaBshJammingState, ssSysStaBshSpoofingState }
    STATUS              current
    DESCRIPTION
        "The Broadshield major alarm has changed state."
    ::= { ssEventsV2 23 }

ssEvtV2HSHealth NOTIFICATION-TYPE
    OBJECTS             { ssHotSwapOverallHealth,
                          ssHotSwapBay1Health,
                          ssHotSwapBay2Health }
    STATUS              current
    DESCRIPTION
        "Hot Swap health has changed."
    ::= { ssEventsV2 24 }

--******************************************************************************
-- Conformance Section [enterprises.18837.3.1.90.x]
--..............................................................................

-- OEM
ssConformance     OBJECT IDENTIFIER ::= { specxSyncMIB 90 }
ssCompliances     OBJECT IDENTIFIER ::= { ssConformance 1 }
ssGroups          OBJECT IDENTIFIER ::= { ssConformance 2 }

ssCompliance      MODULE-COMPLIANCE
    STATUS        current
    DESCRIPTION
        "The compliance statement for SNMP entities which implement version 2
         of the Spectracom xSync MIB"
    MODULE -- this module
        MANDATORY-GROUPS { ssObjectsGroup,
                           ssTrapsGroup }
    ::= { ssCompliances 1 }

-- CONFORMANCE_OEM
ssObjectsGroup    OBJECT-GROUP
    OBJECTS       { ssSysStaPowerDC,
                    ssSysStaTimeReference,
                    ssSysSta1PPSReference,
                    ssSysStaSyncState,
                    ssSysStaHoldoverState,
                    ssSysStaTfom,
                    ssSysStaEstPhaseError,
                    ssSysStaEstFreqError,
                    ssSysStaTimeScale,
                    ssSysStaVersion,
                    ssSysStaTimingVersion,
                    ssSysStaMinorAlarm,
                    ssSysStaMajorAlarm,
                    ssSysStaDateTime,
                    ssSysStaSerial,
                    ssSysStaOscTemp,
                    ssSysStaBrdTemp,
                    ssSysStaCpuTemp,
                    ssSysStaBshJammingState,
                    ssSysStaBshSpoofingState,
                    ssSysStaDisciplining,
                    ssGpsRefInstance,
                    ssGpsReference,
                    ssGpsRefTimeValid,
                    ssGpsRef1ppsValid,
                    ssGpsRefRcvMode,
                    ssGpsRefDynMode,
                    ssGpsRefNumSats,
                    ssGpsRefPdop,
                    ssGpsRefHdop,
                    ssGpsRefVdop,
                    ssGpsRefTdop,
                    ssGpsRefLatitude,
                    ssGpsRefLongitude,
                    ssGpsRefAltitude,
                    ssGpsRefOffset,
                    ssGpsRefAntennaState,
                    ssRefMgmtIndex,
                    ssRefMgmtState,
                    ssRefMgmtPriority,
                    ssRefMgmtTime,
                    ssRefMgmt1PPS,
                    ssRefMgmtTimeValid,
                    ssRefMgmt1PPSValid,
                    ssSysCtrlCommand,
                    ssSysUpdateFile,
                    ssSysSetManualTime,
                    ssHotSwapOverallHealth,
                    ssHotSwapBay1Health,
                    ssHotSwapBay1Type,
                    ssHotSwapBay1Presence,
                    ssHotSwapBay1Voltage,
                    ssHotSwapBay1Current,
                    ssHotSwapBay1FanEnabled,
                    ssHotSwapBay1FanSpeed,
                    ssHotSwapBay1Temp,
                    ssHotSwapBay1VoltageInRange,
                    ssHotSwapBay1CurrentInRange,
                    ssHotSwapBay1FanSpeedInRange,
                    ssHotSwapBay1TempInRange,
                    ssHotSwapBay2Health,
                    ssHotSwapBay2Type,
                    ssHotSwapBay2Presence,
                    ssHotSwapBay2Voltage,
                    ssHotSwapBay2Current,
                    ssHotSwapBay2FanEnabled,
                    ssHotSwapBay2FanSpeed,
                    ssHotSwapBay2Temp,
                    ssHotSwapBay2VoltageInRange,
                    ssHotSwapBay2CurrentInRange,
                    ssHotSwapBay2FanSpeedInRange,
                    ssHotSwapBay2TempInRange }
    STATUS        current
    DESCRIPTION
        "The collection of objects for the Spectracom xSync MIB."
    ::= { ssGroups 1 }

-- NOTIFICATION_OEM
ssTrapsGroup      NOTIFICATION-GROUP
    NOTIFICATIONS { ssEvtV2TimeSync,
                    ssEvtV2Holdover,
                    ssEvtV2FrequencyError,
                    ssEvtV2FrequencyOK,
                    ssEvtV2UserMinorAlarm,
                    ssEvtV2UserMinorClear,
                    ssEvtV2UserMajorAlarm,
                    ssEvtV2UserMajorClear,
                    ssEvtV2GpsAntenna,
                    ssEvtV2MinorAlarm,
                    ssEvtV2MajorAlarm,
                    ssEvtV2RefChange,
                    ssEvtV21ppsError,
                    ssEvtV21ppsOK,
                    ssEvtV2HwError,
                    ssEvtV2OscillatorAlarm,
                    ssEvtV2OscillatorOK,
                    ssEvtV2Reboot,
                    ssEvtV2MaxTempMinorAlarm,
                    ssEvtV2MaxTempMinorClear,
                    ssEvtV2MaxTempMajorAlarm,
                    ssEvtV2MaxTempMajorClear,
                    ssEvtV2BshMajorAlarm,
                    ssEvtV2HSHealth }
    STATUS        current
    DESCRIPTION
        "The collection of traps for the Spectracom xSync MIB."
    ::= { ssGroups 2 }

END